WARNING: Improper installation,adjustment, alteration, service or maintenance cancause injury or property damage. Refer to this manual.For assistance
10To clean the pilot burner and/ or the pilot orifice : Turnoff the gas at the unit. Remove the cover of the heater. Todo so, remove incandescent part
11C. Gas regulator may be shut or damaged.2. In-line AquaStar gas regulator jammed (usually onLP gas)Replace or unjam the regulator. Note: The regulat
12temperature relay for the primary circulator pump is possiblyset too high.WATER IS NOT HOT ENOUGH1. Water flow rate is too high.Decrease the flow ra
13Fig. 10 - Diagram of AquaStar 125 BL 2 4 6 7 15810 1. Heat exchanger 2. Pilot assembly 3. Burner manifold gaspressure test nipple 4. Pilot ga
14Fig. 11 - INTERIOR COMPONENTS DIAGRAM AND PARTS LIST
15Fig. 11INTERIOR COMPONENTS DIAGRAMAND PARTS LIST 125BL1 Cover ¤ 8 705 421 0312 Cap cover ¤ 8 703 304 0113 Water connection gasket ¤ 8 710 103 043
Replacement Parts available from North AmericanDistributorCONTROLLED ENERGY CORP.340 Mad River ParkWaitsfield, Vermont 05673Phone 800-642-3111Fax (802
2This well engineered, gas water heater has beenspecially designed to operate as a circulating waterheater.FEATURES- High Quality Materials for Long W
3D861_059MINIMUM INSTALLATION CLEARANCES FROM COMBUSTIBLE AND NONCOMBUSTIBLE MATERIALS FOR ALCOVE OR CLOSET INSTALLATIONSFRONT VIEW SIDE VIEWAQUASTAR
4If you are using the AquaStar for combined space heating and potable water heating (seeschematic diagram below), all piping and other components conn
57. Correct gas pressure is critical for the optimumoperation of this heater (see specifications on page 2). Gaspiping must be sized to provide the re
6dilution of flue gases.Appliances located in confined spaces:) The confined spacemust be provided with two permanent openings, onecommencing within 1
7Fig. 3 - Flue Adaptor for High Altitude CanadianInstallationsWARNING: Failure TO INCREASE THE VENT SIZETO SIX INCHES AND/or assure that the manifold
8THREADED ASSEMBLYSWEATED ASSEMBLY1/2” FLEXPIPE PRV TOAPPROPRIATEDISCHARGES FITTINGPIPE PRV TOAPPROPRIATEDISCHARGE1/2” FLEXFig. 6-Plumbing connections
9Fig. 7 - Pressure Relief ValveConnecting the pressure relief valve (PRV)A listed pressure relief valve supplied with the heater mustbe installed at t